| 1.0 |
SCOPE |
| |
1.1 |
This specification covers jacketed cables containing
two listed Sprinkler Systems Wires, single conductor, suitable
for direct burial, for operation up to 600 volts, and temperatures
up to 60ºC. |
| |
|
|
| 2.0 |
CONSTRUCTION: |
| |
2.1 |
Inner Conductors: |
| |
|
Soft drawn bare copper meeting the requirements
of ASTM specification B-3 or B-8. Insulation shall be low density
high molecular weight polyethylene and a thickness of 0.045",
per Paige Electric specification P7079D. The two conductors
(blue and red) shall be twisted with a minimum lay of 4". |
| |
2.2 |
Overall jacket: |
| |
|
High density polyethylene with a thickness of
0.035". Available with different color jackets. The jacket shall
be sufficiently round, and loose, to facilitate its removal
when being stripped. |
| |
|
|
| |
2.3 |
Surface Print: |
| |
|
2.31 |
Inner Conductors – “Paige Electric P7079D 14 AWG PE
Listing file Number 600V Sprinkler System Direct Burial” |
| |
|
2.32 |
Outer Jacket – “Paige Electric, P7354D, 14 or 12 AWG PE
600V Sprinkler System Wire Direct Burial Only for Hunter
Decoder Systems RoHS” |
|
|
| 3.0 |
TEMPERATURE RATING |
| |
3.1 |
Color Code: |
| |
|
-55ºC to +60ºC |
| |
|
|
| 4.0 |
PUT-UPS |
| |
4.1 |
1000' (328m), 2500' (762m) and some odd
lengths. |
| |
|
|
| 5.0 |
SPLICING RECOMMENDATIONS |
| |
Wire splices are the weak link of any
electrical circuit. It is especially important to make
proper joints in irrigation systems because the joints are
exposed to wet and damp environments that can cause
corrosion of the copper conductor, and premature failure.
Paige Electric recommends the strict use of Model DBR/Y-6,
as manufactured by the 3M Company (Paige specification
P7364D). |
|