Available colors, stripes, & put-ups

P.O. Box 368, Union, NJ 07083-0368, 908-687-7810, 800-327-2443, Fax: 908-687-8860

PDF Download printable PDF version
TYPE: THHN/THWN
INSULATION: POLYVINYL CHLORIDEINSULATION
JACKET: NYLON
1.0 SCOPE:
1.1 This specification covers the construction requirements for building wire for general purpose applications, including irrigation systems, and may be installed in conduit or other recognized raceways, in wet or dry conditions, up to 600 volts, in accordance with the National Electric Code. Federal Specification J--C-30B.
2.0 CONSTRUCTION:
2.1 Conductor:
Stranded or solid soft drawn bare copper meeting the following ASTM requirements: B-3, B-8, and B-787 for 14-10 AWG B-8 and B-787 for 8-2AWG B-8 for 1/0-1000 MCM
2.2 Insulation:
Extruded polyvinyl chloride with an overall nylon jacket.
2.3 Temperature Rating:
For general application, 75°C wet or 90°C dry.
2.4 Surface Print:
Manufacturer’s identification, conductor size and type, voltage rating, and UL file number.
2.5 Underwriter’s Laboratories Approval:
  UL-83 for THHN/THWN
UL-1063 for MTW
UL-758 for AWM
SIZE AWG
or
MCM
STRANDING INSULATION
THICKNESS
(MILS)
NOMINAL
O.D
(INCHES)
APPROXIMATE
SHIP
WEIGHT
LB/MFT
PVC NYLON
14 SOLID 15 4 .102 17
12 SOLID 15 4 .118 25
10 SOLID 20 4 .150 39
14 19 15 4 .110 18
12 19 15 4 .120 27
10 19 20 4 .161 40
8 19 30 5 .212 69
6 19 30 5 .250 109
4 19 40 6 .318 166
2 19 40 6 .375 254
1/0 19 40 7 .470 398
2/0 19 50 7 .515 488
3/0 19 50 7 .565 603
4/0 19 50 7 .620 731
250 37 60 8 .730 903
300 37 60 8 .780 1060
350 37 60 8 .830 1211
400 37 60 8 .880 1332
500 37 6 8 .970 1735
600 61 70 9 1.060 1990
750 61 70 9 1.170 2468
1000 61 70 9 1.300 3263