P.O. Box 368, Union, NJ 07083-0368, 908-687-7810, 800-327-2443, Fax: 908-687-8860
|
|
| TYPE UF/ NMC-B INSULATION: PVC JACKET: PVC |
![]() |
| SIZE: 14 - 6
AWG, 2 OR 3 CONDUCTOR WITH OR WITHOUT GROUND, 600 VOLTS, 60ºC WET OR DRY |
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
3.0 Cable Data
|
SIZE (AWG) |
STRAND NO. / O.D. (INCHES) |
PVC
INSUL. THICK. (INCHES) |
JACKET THICK. (INCHES) |
APPROX. OUTSIDE DIAM. (INCHES) |
AMPACITY* UF OR NMC-B 60ºC |
APPROX. WEIGHT 1K FT.(LBS) |
STANDARD PUTUPS* |
| SINGLE CONDUCTOR | |||||||
| 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 |
Solid Solid Solid Solid 7/.0612 7/.0772 7/.0972 19/.0745 19/.0837 19/.0940 19/.1055 |
.060 .060 .060 .080 .080 .080 .080 .095 .095 .095 .095 |
- - - - - - - - - - - |
.188 .205 .226 .296 .352 .400 .460 .573 .618 .670 .728 |
15 20 30 40 55 70 95 125 145 165 195 |
28 38 52 87 123 183 270 415 508 634 782 |
500/2500 2500 2500 2500 1000 1000 1000 1000 1000 1000 1000 |
| TWO AND THREE CONDUCTOR - WITHOUT GROUND | |||||||
| 14/2 12/2 10/2 8/2 6/2 14/3 12/3 10/3 8/3 6/3 |
Solid Solid Solid 7/.0486 7/.0612 Solid Solid Solid 7/.0486 7/.0612 |
.030 .030 .030 .045 .060 .030 .030 .030 .045 .060 |
.030 .030 .030 .045 .045 .030 .030 .030 .045 .045 |
.210 x .435 .220 x .445 .240 x .475 .340 x .700 .410 x .900 .210 x .600 .215 x .640 .245 x .700 .345 x 1.040 .415 x 1.260 |
15 20 30 40 55 15 20 30 40 55 |
67 84 114 206 326 98 128 172 308 469 |
C250/R1500 C250/R1250 C250/R1000 C125/R500 C125/R500 C250/R750 C250/R500 C250/R500 C125/R500 C125/R500 |
| TWO AND THREE CONDUCTOR - WITH GROUND | |||||||
| 14/2 12/2 10/2 8/2 6/2 14/3 12/3 10/3 8/3 6/3 |
Solid Solid Solid 7/.0486 7/.0612 Solid Solid Solid 7/.0486 7/.0612 |
030 .030 .030 .045 .060 .030 .030 .030 .045 .060 |
.030 .030 .030 .045 .045 .030 .030 .030 .045 .045 |
.210 x .445 .235 x .495 .240 x .570 .340 x .700 .410 x .900 .210 x .650 .225 x .720 .245 x .800 .345 x 1.040 .415 x 1.260 |
15 20 30 40 55 15 20 30 40 55 |
78 109 155 230 383 110 147 218 346 519 |
C250/R1500 C250/R1250 C250/R1000 C125/R500 C125/R500 C250/R750 C250/R500 C250/R500 C125/R500 C125/R500 |
| * Allowable ampacity of not more than
three conductors in raceway or cable or earth (directly buried), based on ambient temperature of 30ºC (86ºF), per Table 310-16 of the 1987 Nat'l Electrical Code (NFPA 70 · 1987 |
** Standard Put-Ups: C - Coils R - Reels |