| 1.0 |
SCOPE: |
|
1.1 |
For connecting the 24 volt irrigation controller
outputs to the solenoid valves. Also used in many other direct
burial applications. |
| 2.0 |
PHYSICAL SPECIFICATIONS: |
|
2.1 |
Multiple conductors of solid bare copper meeting
ASTM B-3, insulated with .015" of 80°C color coded PVC insulation,
are cabled with .025" of an extruded PE jacket with a nylon
rip cord. This cable is suitable for direct burial, rated 30
volts UL listed. Outer Jacket is UV and sunlight resistant. |
| 3.0 |
MANUFACTURER’S IDENTIFICATION: |
|
|
Surface marked with Paige Electric P7183D, 18
AWG and number of conductors, 30V, direct burial sprinkler system
wire, UL file number, sequential footage every 2 feet
maximum. |
| |
|
|
| 4.0 |
SPLICING RECOMMENDATIONS |
| |
4.1 |
Underground splices shall be made in accordance with National Electrical Code® Articles 300.5 (Underground Installations) and 110.14 (Electrical Connections) using 3M DBY-6 or DBR-6 connectors, which are UL listed under
"UL 486D-Direct Burial", for wet or damp locations, 600 volts. Connectors that are not listed at all, or listed under UL Standard UL 486C as
"Compression Connectors", shall not be allowed. |
| |
|
|
| 5.0 |
CONSTRUCTION: |
| |
5.1 |
Put-Ups: |
| |
|
250, 500, 1000 and 2500 feet.
Other custom put-ups available
upon request. |