1.1 |
This specification covers requirements for
a armored direct burial shielded multiconductor cable designed to send
signals, or power from field controllers and sensing devices back to a
central controller or computer, utilizing stranded UL listed PVC/nylon
insulated conductors UL listed type TFN cabled with fillers, having an
aluminum shield and drain wire to drain off electrical, magnetic or RF
interference, and a .005" stainless steel helically wrapped armor over
the core and a direct burial sunlight resistant PVC Jacket overall. This
cable is rated at 600 volts and offers complete protection against
gophers and other rodents. |
| 2.0 |
CONSTRUCTION: |
|
2.1 |
|
NO. OF
COND. |
SIZE |
STRAND |
INSULATION
WALL (MILS) |
UL TYPE |
| 2 |
16 |
7 |
.015PVC/.005 NYLON |
TFN |
|
|
2.2 |
Color Code:
Yellow, Grey: |
|
2.3 |
Conductors:
Stranded soft annealed tin coated copper conforming to ASTM-B-3 and B-8. |
|
2.4 |
Insulation:
Polyvinyl Chloride and nylon conforming to UL Type TFN rated 90ºC dry and 75ºC wet. |
|
|
| 2.5 |
Cable Assembly: |
|
Insulated conductors are cabled with fillers
to ensure roundness. |
| 2.6 |
Shield:
A 2 mil aluminum backed polyester shielding with a #16 AWG solid tinned copper drain wire
in contact with the aluminum side with a 25% minimum overlap. |
| 2.7 |
Armor:
A .005" x .500" type 304 stainless steel tape is helically wrapped around the
core with a minimum of 25% overlap. |
| 2.8 |
Jacket:
Sunlight resistant PVC conforming to ICEA S-61-40, NEMA WC5 and UL 1277. Nominal thickness
.050". |
| 2.9 |
Surface Print:
Paige P7162D-A No. of conductors size 600V shielded and armored direct burial type TC
(UL), Tuf-hide®. On opposite side ink print sequential footing. |
| 3.0 |
Paige Part Number:
180096TH
NOTE: For use on Toro Control Systems in areas where gopher protection is necessary. |
|