Available colors, stripes, & put-ups

P.O. Box 368, Union, NJ 07083-0368, 908-687-7810, 800-327-2443, Fax: 908-687-8860

PDF Download printable PDF version
DIRECT BURIAL
GOLF COURSE SPRINKLER WIRE
INSULATION: POLYETHYLENE
SIZES: 14 AWG - 10 AWG SOLID
Ullogo.gif (224 bytes)
1.0 SCOPE:
1.1 This specification covers single conductor insulated wire sizes 14 AWG, through 10 AWG, utilizing low density high molecular weight polyethylene insulation, suitable for direct burial applications for operating temperatures up to 60°C. UL and c(UL) listed.
2.0 CONSTRUCTION:
2.1 Conductor:
Soft drawn bare copper meeting the requirements of ASTM specifications B-3 0r B-8.
2.2 Temperature Rating:
-55ºC + 60ºC
2.3 Insulation Thickness:
.045"
  2.4 Sunlight Resistance:
    Available as an option
2.5 Manufacturer's Identification:
Surface marked with Paige-Electric, voltage rating, size and type, and UL file number
     
2.6 Underwriters' Laboratories Approval:
All cables shall be tested physically and electrically in accordance with UL Standard 493, and 83 (paragraphs 28.1,29.1 and 29.2). All reels and cartons bear UL labels.
2.7 Tests:
Material must be able to pass the following tests without showing signs of degradation.
2.7.1 COLD BEND:
The insulation shall not show any cracks when sample is bent around a mandrel of 3 x wire diameter, after being subjected to -55°C ± 1°C for one (1) hour.
2.7.2 ELECTRICAL:
AC test voltage, 5 minutes at 3,000 volts.
 
    2.7.3 ENVIRONMENTAL AGING:
Immersed for 14 days in concentrated solutions of fertilizers, herbicides and insecticides.
  2.8 INSULATION COMPARISON WITH
PVC TYPE UF AND TWU - 40
  PE PVC TYPE
UF
PVC TYPE
TWU-40
TEMPERATURE RANGE -55º +60ºC -10º +60ºC -55º +60ºC
TENSILE STRENGTH 1400 PSI 1500 PSI 1800 PSI
INS. RES. (MEG.OHMS/1000') 50,000 200 152
ELONGATION EXCELLENT GOOD GOOD
MOISTURE RES. EXCELLENT GOOD FAIR
COLD BEND EXCELLENT GOOD EXCELLENT
ABRASION GOOD GOOD FAIR
     
  2.9 UL Listed for 600 Volts
c(UL) Listed for 30 Volts.
     
3.0 SPLICING RECOMMENDATIONS
  3.1 Underground splices shall be made in accordance with National Electrical Code® Articles 300.5 (Underground Installations) and 110.14 (Electrical Connections) using 3M DBY-6 or DBR-6 connectors, which are UL listed under "UL 486D-Direct Burial", for wet or damp locations, 600 volts. Connectors that are not listed at all, or listed under UL Standard UL 486C as "Compression Connectors", shall not be allowed.