Available colors, stripes, & put-ups

P.O. Box 368, Union, NJ 07083-0368, 908-687-7810, 800-327-2443, Fax: 908-687-8860

PDF Download printable PDF version
UNDERGROUND
FEEDER CABLE (UF) & TWU

INSULATION: POLYVINYL CHLORIDE
SIZES: 14 AWG - 4/0 AWG
P7264D
Ullogo.gif (224 bytes)
1.0 SCOPE:
  1.1 This specification covers the construction requirements for Underground Feeder Cable, Type UF and TWU, for use in accordance with the National Electrical Code or operation at a potential of 600 Volts or less and at a temperature of 75°C or less. UL listed for UF and c(UL) for TWU
     
2.0 CONSTRUCTION:
  2.1 Conductor:
Soft drawn bare copper meeting the requirements of ASTM specification B-3 or B-8.
     
  2.2 Temperature Rating:
-10°C +75°C.
     
  2.3 Insulation:
Polyvinyl chloride, 75°C rated conforming to UL Standards 493 and 83.
     
  2.4 Manufacturer's Identification:
Surface marked with Paige-Electric, voltage rating, size and type, and UL file numbers.
     
  2.5 Underwriters' Laboratories Approval:
All cables shall be tested physically and electrically in accordance with UL Standard 493, and 83 (paragraphs 28.1, 29.1 and 29.2). All reels and cartons bear UL and/or c(UL) labels.
     
3.0 PARALLEL CONSTRUCTION:
 
 
  3.1 Multiple wires, of varying sizes and colors, are bound together with a reinforced filament tape in a helical fashion.
     
SIZE AWG STRANDING INSULATION WALL (MILS) APPROX. DIAMETER (INCHES) CURRENT CARRY CAPACITY*
14 SOLID .060 .190 15
12 SOLID 0.060 0.205 20
10 SOLID 0.060 0.225 30
8 SOLID 0.080 0.285 40
14 7 0.060 0.200 15
12 7 0.060 0.215 20
10 7 0.060 0.240 30
8 7 0.080 0.300 40
6 7 0.080 0.340 55
4 7 0.080 0.390 70
2 7 0.080 0.450 95
1 19 0.095 0.520 110
1/0 19 0.095 0.560 125
2/0 19 0.095 0.605 145
3/0 19 0.095 0.660 165
4/0 19 0.095 0.715 195
*Current carrying capacity based on not more than 3 conductors in raceway or cable or direct burial (at room temperature of 30°C)
 
4.0 SPLICING RECOMMENDATIONS
  4.1 Underground splices shall be made in accordance with National Electrical Code® Articles 300.5 (Underground Installations) and 110.14 (Electrical Connections) using 3M DBY-6 or DBR-6 or 82A series connectors, which are UL listed under "UL 486D-Direct Burial", for wet or damp locations, 600 volts. Connectors that are not listed at all, or listed under UL Standard UL 486C as "Compression Connectors", shall not be allowed.