DB14-4 DIRECT BURY INSTRUCTION SHEET
SPLICE KIT # 270DB144
 |
- Connector kit for splicing wires in underground installations.
- Accommodates up to 3 wires, each ranging from 14 to 4 AWG, solid or
stranded.
- 600 Volts maximum
- Designed to meet Articles 300.5 (Underground
Installations) and 110.14 (Electrical Connections)
of the 2005 National Electrical CodeŽ, under ULŽ
486D-Direct Burial.
- Resistant to the ultraviolet rays of the sun.
- Cable tie provides strain relief so the connection doesn't
come apart when the wires are pulled-upon.
- Application temperature is 32 to 120°F (0 to 49°C)
- Storage temperature: 120°F (49°C) maximum.
- Child resistant. Re-enterable, not re-usable.
|
Packaging:
- Ten 3-Packs of connector assemblies per case
- Each 3-Pack (in a sealed plastic bag) includes the following components,
for making 3 splices:
3 each gel-filled enclosures
3 each bus bar connectors
3 each cable ties
1 each Allen wrench
1 each Instruction Sheet
Important Notice:
Turn off power before installing or removing connector. All electrical
work should be done according to appropriate electrical codes. Before utilizing
these products, the user should determine the suitability of the product for its
intended use. Paige Electric Co., LP expressly disclaims the implied warranties
and conditions of merchantability and fitness for a particular purpose. In no
case shall Paige Electric Co., LP be liable under any legal theory, including
but not limited to contract or strict liability, for any direct, indirect,
special, incidental or consequential damages resulting from product use.
Installation Instructions:
- Strip 3/8" to 1/2" (9.5 to 12.7 mm) of the wires' insulation.
- Insert wires securely into the connector bar and tighten the hex head
screws by using the included Allen wrench as shown in Figure 1. Tape wires
together with electrical tape about 5" (12.7 mm) from the end of the
connector bar as shown in Figure 2. Tighten screws again to a minimum torque
of 45 inch-pounds, to make sure the wires are secure. The wire conductors
should not stick out more than 1/4" (6.4 mm) from the end of the bus bar, as
shown in Figure 1. Trim the wire conductors if necessary. Note that if the
wire conductors stick out more than 1/4" (6.4 mm), the connector bar will
not lock in place and a new kit will have to be used.
- Insert the connected wires and connector bar into the gel-filled
enclosure so it bottoms out and until it slides past the locking ramps.
Close the lid and snap it shut as shown in Figure 3.
- Thread the included cable tie through the slotted holes and secure the
wires to the connector body as shown in Figures 3 and 4. Pull the cable tie
tightly around the wires. The excess of the cable tie may be trimmed if
desired.
Undoing the Splice:
The connection can be taken apart if necessary. For safety reasons,
child-resistant locking tabs (2 on each side, as shown in Figure 5) must be
depressed while pulling gently on the wires. Use a small screw driver or pointed
tool to depress the tabs, then pull on the wires. Re-make the slice using a new
DB14-4 Connector Kit. DO NOT RE-USE THE CONNECTOR AFTER TAKING IT APART.