82-A and 82-B1 Series

Inline Resin Splice Kits for 1 and 5 kV

Use the 3M Scotchcast 82-A and 82-B1 series kits to insulate and seal single conductor, unshielded cable splices through 5 kV and multiple conductor cables through 1 kV. 82-A is for inline splices and the 82-B1 is for Wye splices.

Each kit contains:

  • Snap-together mold body
  • 2 Funnels
  • Tape for sealing mold ends and connector area
  • Scotchcast 4 electrical insulating resin in a Unipack container

Each kit makes one splice

The 82-A series is UL Listed 486D, File Number E102356.
Cu or Al connectors are not included, order separately.

P1.gif (44779 bytes)
 
Product UPC Conductor
Size*

Maximum
Cable O.D.

Maximum
Connector O.D.
Sleeve Type
Inner
Unit
Pack
Case
Qty.
82-A 25016 10 - 2 AWG
(6 to 30 mm2)
0.750"
(19 mm)
0.406"
(10 mm)
1/box 10
82-A1 25024 Up to 2 AWG
(30 mm2)
0.625"
(16 mm)
0.406"
(10 mm)
1/box 10
82-A2 25032 2 to 3/0 AWG
(35-80 mm2)
1.000"
(25 mm)
0.625"
(16 mm)
1/box 10
82-A3 25040 3/0-400kcmil**
(95-200 mm2)
1.563"
(40 mm)
1.000"
(25 mm)
1/box 10
82-B1 25057 up to 2 AWG
(30 mm2)
0.625"
(16 mm)
- 1/box 10
*Important: Use insulation jacket or connector O.D. for final ordering criteria.
** 500 kcmil when using a scotchlock 10014 copper compression connector.
 
IMPORTANT NOTICE TO PURCHASER:
All statements, technical information and recommendations related to the Seller's products are based on information believed to be reliable, but the accuracy or completeness thereof is not guaranteed. Before utilizing the product, the user should determine the suitability of the product for its intended use. The user assumes all risks and liability whatsoever in connection with such use.
All statements or recommendations of the Seller which are not contained in the Seller's current publications shall have no force or effect unless contained in an agreement signed by an authorized officer of the Seller. The statements contained herein are made in lieu of all warranties expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose which warranties are hereby expressly disclaimed.

© 3M 1993

SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANY LEGAL THEORY, INCLUDING BUT NOT LIMITED TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY OR FOR ANY DIRECTOR CONSEQUENTIAL DAMAGES SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY OF THE SELLER'S PRODUCTS.
3M Electrical Products Division 6801 River Place Blvd. Austin, Texas 78726 - 9000

3M